PM1000 Series Power Meters PLSED309039EN
Appendix A: Technical Data 08/2010
© 2010 Schneider Electric. All rights reserved.
Password protection for setup parameters.
User-selectable default display page through keypad lock.
Installation and Input Ratings
Auto-ranging voltage inputs should allow direct connection up to 277
VLN/480VLL AC systems, no PTs (VTs) required up to 480 VLL phase to
phase).
Supports the following configurations (field configurable):
Direct 4-wire Wye (Star); 3-wire Wye (Star); 3-wire Delta; 2-phase 3-wire
(2-phase), and single-phase.
3-phase voltage, and current inputs
Volts : 46 to 277 VAC phase-neutral, 80 to 480 VAC phase-phase,
Overload: Continuous 480 VLL with full accuracy, 750 VLL Max, Hz. 50 /
60
Amps: 50 mA to 6 A, Overload: 10 A continuous, 50 A for three seconds
User programmable for 5 A or 1 A secondary CTs
Burden (Load): Less than 0.2 VA per Volt / Ampere input
Frequency (Both input and auxiliary): 50 / 60 Hz, 45 to 65 Hz
Environmental Conditions
Sealed dust- proof construction. Meets IP51 for the front panel and IP40
for rear panel.
Operating temperature: -10 C to 60 C , (14 F to 140 F)
Storage temperature: -25 C to 70 C, (-13 F to 158 F)
Humidity: 5% to 95%, non-condensing
Construction
Self-extinguishable V0 plastic, double insulation at accessible areas.
Pollution Degree II.
Measurements Category III.
Dimensions and Shipping
Basic unit installed depth 82 mm (3.23 in.) with the protected cover with 92
x 92 mm (3.62 x 3.62 in.) panel cutout, flush mount.
Bezels dimension 96 x 96 mm (3.78 x 3.78 in.). Panel Cut-out 92x92 mm
(3.62 x 3.62 in.).
Weight 400 gms (0.9 lb) approx unpacked, 500 gms (1.1 lb) approx
shipping. See ―Mechanical Installation‖ on page 35 for more information.