PM1000 Series Power Meters PLSED309039EN
Chapter 5 Installation 08/2010
44
© 2010 Schneider Electric. All rights reserved.
3-phase 3-wire delta connection with two CTs and three PTs
Direct voltage connections for the input voltages L-L up to 480 VAC.
Figure 5-4: 3-phase 3-wire delta connection
NOTE : Make sure Delta is programmed in the power meter PROG menu- setup. Leave the Vn
terminal disconnected.
3-phase 3-wire open delta connection with two CTs and two PTs
Direct voltage connections for the input voltages L-L up to 480 VAC.
Figure 5-5: 3-phase 3-wire open delta connection
NOTE: Make sure Delta is programmed in the power meter PROG menu-setup.
Use PT, if
VAC LL 481 V
0.25 A
Aux supply
(Control Power)
44 to 277 VAC/DC
LOAD
LINE
Communication
(PM1200)
PT
L1 L2 L3
80 t o 480 Vac LL
VER:03.04.00
D- D -IERS 485- TH M
Op t i o n List :
RS 485
mA to 6A
50
S
/
N:
COYYWWDXXXX Acc Cl: 1.0
44 to 277 V 50/60 Hz <5 VA
Use PT, if
VAC LL 481 V
0.25 A
Aux supply
(Control Power)
44 to 277 VAC/DC
LOAD
LINE
Communication
(PM1200)
PT
L1 L2 L3