Schneider Electric K series Manual do Utilizador Página 16

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 15
PM1000 Series Power Meters PLSED309039EN
Chapter 1 PM1000 Series Power Meters Product Description 08/2010
16
© 2010 Schneider Electric. All rights reserved.
PM1000 Series Power Meters Technical Specification
The PM1000 series is a high-accuracy, low cost, ultra-compact, power, and
energy meter series. It offers ISO 9001 quality, accuracy and functional
flexibility. Selective models of this series have Modbus RTU
communications capability. The standard unit flush-mounts in a DIN 96
cutout and conforms to UL product standards.
The power meters are designed for retrofit applications such as replacement
of analog meters. Each can be used as standalone meter in electrical
control panels, power distribution unit (PDU), switch boards, uninterrupted
power supply (UPS), generator sets, and motor control center (MCC)
systems. It also provides easy communication to program logic control
(PLC), distributed control system (DCS), building management system
(BMS), and other systems.
The following table gives the technical specifications of the power meters.
Refer to ―Technical data‖ on page 71 for more information.
Table 1-6: Technical specifications
Description
Specification
Sensing/Measurement
True RMS, one second update time, four quadrant power
and energy
Accuracy
1.0% of reading*
Auxiliary supply
(Control power)
44 to 277 VAC/DC
Burden
Voltage and current input < 0.2 VA per phase
Auxiliary supply (Control power) < 3 VA at 240 V
Display
Alphanumeric bright LED
Resolution
RMS four digits, INTG eight digits
Input voltage
Four voltage inputs (V1, V2, V3, VN) 110 or 415 VACLL
nominal (Range 80 to 480 VAC LL)
Input current
(Energy measurement)
Current inputs (A1, A2, A3)
Class 1.0: 50 mA to 6 A* (5 mA is the starting)
Frequency
45 to 65 Hz
Overload
10 A max continuous
Environmental
Operating temperature: -10 C to 60 C (14 F to 140 F)
Storage temperature: -25 C to +70 C (-13 F to 158 F)
Humidity 5% to 95% non condensing
Standard
- Measurement category III,
Pollution Degree 2,
- Double insulation at user-accessible area
Weight
400 gms (0.9 lb) approx, unpacked
500 gms (1.1 lb) approx, shipping
Communication
(PM1200)
RS 485 serial channel connection Industry standard Modbus
RTU protocol
PM1000 Series
conforms to
Emission : CISPR11 class A; Fast Transient: 4kV IEC
61000-4-4; Surge withstand: IEC 61000-4-5;
Damped Oscillatory: IEC 61000-4-12; ESD: IEC 61000-4- 2;
Impulse voltage: 6 kV, IEC 60060, 1.2/50 µs
Protection against dust
and water
Front IP 51; Back IP 40
NOTE: * Additional error of 0.05% of full scale, for power meter input current below 100 mA