PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 7 Maintenance And Troubleshooting
© 2010 Schneider Electric. All rights reserved.
69
Potential Problem
Possible Cause
Possible Solution
The display went blank
suddenly.
Over voltage/temperature
Interrupt the power supply
or reduce the voltage or
temperature within the
limit.
Fuse connection
Check whether a fuse with
rating of 0.25 A is
connected on each
voltage input. If not
connect the 0.25 A rated
fuse to the voltage input.
The power meter stopped
communication abruptly.
Communications lines are
improperly connected.
Verify the power meter
communications
connections. See ―Chapter
6 Data communication‖
on page 47 for more
information.
Over voltage/temperature
Interrupt the power supply
or reduce the voltage or
temperature within the
allowable limits.
Wrong Load bar indication
Incorrect F.S% selection
Select the full scale load
percentage setting as per
your circuit.
The Power meter is over
heated
Lack of sufficient air for
cooling
Provide sufficient space all
around the power meter.
Separate the power meter
from other equipment for
cooling air.