PM1000 Series Power Meters PLSED309039EN
Chapter 6 – Data Communication 08/2010
© 2010 Schneider Electric. All rights reserved.
Figure 6-2: Closed loop, 2-wire half duplex.
Advantage – Reliable communications, tolerant to one break in the
cable.
Communication Capabilities
Table 6-1: RS 485 communication distances
NOTE: Distances listed should be used as guide only and cannot be guaranteed for non-
PowerLogic devices. Above distances subject to vary based on the quality of the cable.
Daisy-chaining Devices to the Power Meter
RS 485 slave port allows the power meter to be connected in a daisy chain
with up to 31 2-wire devices. In this bulletin, communications link refers to a
chain of devices that are connected by a communications cable. See Figure
6-3.
Figure 6-3: Daisy-chaining 2-wire devices
NOTE: Belden 3105A/9841 colors: Blue (+), White (-)
If the power meter is the first device on the daisy chain, connect it to the
host device using a RS 232 to RS 422/RS 485 converter or RS 485 to
Ethernet converter.
PM1200 power meters rear view
RS485
communication port
RS485 Data
Converter
RS485
RS232
+
G
-
Maximum communication distances 1 to 32 devices
Meters ( Typical with Belden 3105A cables)
Power Meter 1200 or other POWERLOGIC 2-wire compatible devices