PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 1 PM1000 Series Power Meters Product Description
© 2010 Schneider Electric. All rights reserved.
15
Parameter
PM1000
PM1200
OLD
REV
R.Wh
R.VAh
R.VARh
-R.VARh
Run hours
OLD
TOT
t.Wh
t.VAh
t.VAR
-t.VAR
t.Run
RS 485
-
NOTE:
FWD: Forward indicating the import of power into the plant/grid
REV: Reverse indicating the export of power from the plant/grid
The PM1000 series displays:
Voltage: Three voltage measurements line-to-line: 1-2, 2-3, 3-1, and
average, Three voltage measurements line-to-neutral: 1-4, 2-4, 3-4, and
average.
Current: Three current measurements phase-wise (1, 2, 3), average
current of all three phases, neutral current, and three current phase angles
(A
1, A
2, A
3) with respect to the corresponding voltage line-neutral
vector.
Phase wise load in %: Three currents in % of the FS (%A FS).
Unbalanced load in %: Current and voltage unbalance.
Frequency: Measures from whichever phase is active.
RPM: Measures the speed of the generator.
Power: VA, W, VAR, per phase and total. PF per phase and average. Per-
Phase W readings provide a quick CT Polarity Check. A negated W phase
reading indicates CT reversal.
Energy: VAh, Wh, +VARh (Ind), -VARh (Cap), Run hours, On Hrs, supply
interruptions (outage).
Energy (OLD): VAh, Wh, +VARh (Ind), -VARh (Cap), Run hours.
% Amperes load bar graph: Load bar graph indicates consumption in
terms of %Amperes total. You can quickly estimate the load by viewing the
display without operating any keys. The bar graph consists of 12
segments. Each segment indicates a current load of 10% of CT primary.
Kilo, Mega, Giga indication for the above parameters. See ―The
indicators‖ on page 9 for more information.