Communication Test
Communication test: PM1200 power meter can be successfully used for
communication using Modscan software as Modbus master in PC. Details
of the settings in Modscan are given below.
Settings in Modscan v3.D05-00 software to establish communication
with PM1200 power meters:
Free download demo Modscan software from http://www.win-tech.com.
The following explains how to read apparent power total (VA total) from
register 3901.
1. After starting the Modscan, to read Apparent power total (VA total), enter
address as 3901 (decimal), length as 2, device ID as 1, Modbus point
type as 03, and HOLDING REGISTER.
2. Modify the connection details: Click connection > connect, to see the
connection detail window. Change all the settings to match the
following screen. These are default settings of PM1200 power meter.