Schneider Electric K series Manual do Utilizador Página 62

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 61
PM1000 Series Power Meters PLSED309039EN
Chapter 6 Data Communication 08/2010
62
© 2010 Schneider Electric. All rights reserved.
NOTE: For efficient setup, read the setup parameters first and then edit the required setup
parameter value.
Parameter
Description
Address
Type
Range
Default
value
PM1200
D Prd
Demand
period
0119
Float
1.0 to 6.0
1.0 5 Min
2.0 10 Min
3.0 15 Min
4.0 20 Min
5.0 25 Min
6.0 30 Min
3.000
BAUD
Baud rate
0121
Float
1.0 to 5.0
1.0 1200
2.0 2400
3.0 4800
4.0 9600
5.0 19200
4.000
PRTY
Parity and
stop bit
0123
Float
0.0 to 5.0
0.0 Even 1
1.0 Even 2
2.0 Odd 1
3.0 Odd 2
4.0 No 1
5.0 No 2
0.000
ID
Unit ID
0125
Float
1.0 to 255.0
1.000
F.S%
% Full scale
0127
Float
1 to 100
100.0
OFLo
Overflow
parameter
selection
0129
Float
0.0 to 1.0
0.0 Wh
1.0 VAh
0.000
POLE
Number of
poles for RPM
0131
Float
1.0 to 8.0
1.0 2
2.0 4
3.0 6
4.0 8
5.0 10
6.0 12
7.0 14
8.0 16
2.000
PWD
Password
0133
Float
1000
1000
Reserved
Reserved
0135
Float
-
2.0
Reserved
Reserved
0137
Float
-
4126
Reserved
Reserved
0139
Float
-
0.0
Vista de página 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 80 81

Comentários a estes Manuais