PM1000 Series Power Meters PLSED309039EN
Chapter 2 – Quick Start Guide 08/2010
© 2010 Schneider Electric. All rights reserved.
Demand Power Calculation Methods
Demand power is the energy accumulated during a specified period divided
by the length of that period. How the power meter performs this calculation
depends on the method you select. To be compatible with electric utility billing
practices, the power meter provides the following types of demand power
calculations:
Auto (sliding block)
User (fixed block)
Auto (sliding block)
In the auto demand power calculation, you select an interval between five
and 30 minutes in steps of five minutes. The demand calculation updates
every 15 seconds.
Auto demand power calculation is the default calculation for PM1000 series
power meters.
User (fixed block)
In the user demand power calculation, you select an interval between five
and 30 minutes in steps of five minutes. The demand calculation updates at
the end of the interval. User demand power calculation can be selected
through setup. See ―Setup parameters in View and Edit modes‖ on page 20
for more information.
Demand value is the
average for the last
completed interval
User (Fixed block) demand calculation
Calculation updates
every 15 seconds
Demand value is the
average for the last
completed interval
Auto (Sliding block) demand calculation
Comentários a estes Manuais