CHAPTER 3—DIAGNOSTICS AND TROUBLESHOOTING
Keypad Display and Indicating LEDs
When a fault condition is detected, a fault code and a plain language
message will be displayed as long as power is maintained. See
Table 27 on page 103 for fault codes and messages. In addition, the
LEDs on the front of the drive controller indicate the states illustrated
in Figure 24.
Fault Storage
The first fault detected is saved and displayed on the keypad display
if power is maintained. The drive controller trips, the red fault LED
illuminates, and the fault relay de-energizes. To reset the fault:
1. Remove power from the drive controller.
2. Before restoring power, identify and correct the cause of the fault.
3. Restore power. This will reset the fault if it has been corrected.
Figure 24: Location and Description of LEDs
FAULT
POWER
Other LEDs, display the state with option card installed
Green POWER LED illuminated: drive controller powered
Red FAULT LED
• illuminated: drive controller in fault
state
• flashing: drive controller in fault
state after pressing the keypad
display STOP key in terminal
mode with a forward, reverse, or
DC injection input active, or
following a change to the
configuration. The motor cannot
be started until the Forward,
Reverse, or DC injection inputs are
reset.
Comentários a estes Manuais