© 1998–2003 Schneider Electric All Rights Reserved
Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
58
5—I/O Menu
This menu allows you to assign functions to the inputs and outputs. It
is accessible when the access locking switch is in the total unlock,
, position. The I/O assignments can only be modified if the motor
is not running.
The inputs and outputs displayed in the I/O menu vary depending on
selections made in the 4Control menu and whether or not an I/O
extension card is installed. On the 125–500 hp drive controllers, the
Brake Logic function and I/O associated with torque are not
configurable. The default settings depend on the macro-configuration
selected (see Table 3 on page 24 for factory settings).
BdRate RS485 tbr
Transmission speed on the
RS-485 MODBUS port on the
front of the drive controller.
9600, 19200 19200
9600 Bits / second
19200 Bits / second
NOTE: The keypad display will not operate properly if
parameter tbr is set to 9600. On power up, ERR7 may
show on the display indicating this error.
To reset:
1. Turn off power to the drive controller.
2. Slide the 50/60 Hz switch to the direction opposite its
current position.
3. Power up the drive controller for 3 s.
4. Repeat Step 1.
5. Slide the 50/60 Hz switch to its original position.
6. Power up the drive controller and reenter the correct
user configuration, because the parameters will have
returned to their factory settings.
Reset counters rPr
This parameter sets KWh or
operating time to 0.
No-APH-
RTH
No
No: Ready to accept a reset command.
APH: KWh reset to 0
RTH: Operating time reset to 0
Press “ENT” to confirm the reset to 0 command.
APH and RTH are active immediately. The parameter then
automatically returns to No.
Table 14: 4—Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
These parameters are available only with the I/O extension card installed.
Menu
4