© 1998–2003 Schneider Electric All Rights Reserved
Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
66
Ramp Switching
This function allows switching between the first and second ramps.
The first ramps are ACC and dEC, the second ramps are AC2 and
dE2. There are two ways to activate the function:
• Assign a logic input to RP2 and close the assigned input (set it to
state 1).
• By detection of a frequency threshold. This must be configured
with the Frt parameter.
If a logic input is assigned to the function, ramp switching can only be
initiated by the assigned input.
Jog
A logic input can be assigned to the Jog function to define a motor
speed from 0 to 10 Hz. A run command (FWD or REV) is also
required.
If the Jog contact is closed (set to state 1) and then a run command is
given:
• The acceleration ramp is 0.1 s.
• The deceleration ramp will be 0.1 s when the run command is
removed.
If a run command is given and then the Jog contact is closed (set to
state 1):
• The acceleration ramp (ACC) is 0.1 s if the motor speed is less
than the programmed Jog speed.
• The deceleration ramp (dEC) is followed if the motor speed is
higher than the programmed Jog speed.
When the Jog contact is opened (set to state 0), the ACC and dEC
settings are used to adjust the motor speed.
The following Jog parameters can be modified in the 2—Adjust menu:
• Jog speed (JOG)
• Delay between jog pulses (JGt)
+Speed/-Speed
There are two types of operation for +Speed/-Speed:
1. Use of pushbuttons. Two logic inputs are required in addition to
the run direction inputs. The +Speed input increases the speed