Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
74
Using the Analog Inputs
The AI1 input is set for speed reference unless the PI Regulator
function is enabled. In this case, AI1 is used for the set point
reference. The possible assignments of AI2 and AI3 are Speed
Reference Summing and PI Regulator.
Speed Reference Summing
The frequency references at AI2 and AI3 can be summed with that at
AI1.
PI Regulator
This function is used to regulate a process with a setpoint input and a
feedback signal from the process. The function is enabled by
assigning an analog input (AI) to PI feedback in the 5—I/O menu after
first ensuring that the Auto/Manual (RFC) parameter is not assigned
to a logic input. This function is only available in the Variable Torque
Macro. The acceleration (ACC) and deceleration (dEC) ramps default
to linear ramp type even if the ramps had been configured for S ramp
or U ramp with the rPt parameter.
When the PI regulator is configured and a logic input is configured for
PAU: PI Auto/manual, the PI regulator function is active in Auto mode
and AI3 is used for speed input in manual mode. To use the PI
Auto/Manual function, you must install an analog option card,
VW3A58201U.
Logic inputs can be used with the PI regulator to command the drive
controller to run from the analog reference, run at process maximum,
or operate with two other definable pre-set setpoints. The
configurable setpoints can be used to provide two different setpoints
for two different processes, or they can be used instead of using AI1
for setpoint input. For example, providing a setpoint via the logic
inputs can eliminate the need for a potentiometer.
Four analog outputs are available to monitor various aspects of the PI
regulator function. See pages 83–84 for more information.
Figure 18 shows a diagram of the PI Regulator inputs, calculation
points, and outputs.
PI setpoint OPS PI feedback OPF
PI error OPE PI integral error OPI