Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
70
Reference Switching (Auto/Manual)
Switching between two references (at AI1 and AI2) by a logic input
command. When the logic input is closed (set to state 1), AI1 is
enabled. This function automatically assigns AI2 to Speed
Reference 2.
Freewheel Stop (Coast to Stop) / Run Permissive
A logic input can be assigned to the Freewheel Stop / Run Permissive
(NST) function. The drive controller will not run until the logic input is
closed. Opening the logic input assigned to the function (setting it to
state 0) causes the drive controller to stop applying power to the
motor and the motor to coast to a stop. When the logic input is open,
NST is displayed in the Drive state screen on the keypad display to
indicate that a freewheel stop has been requested. The drive
controller will not run until the logic input is closed. This can be used
with the Forced Local function for drive controllers on communication
networks.
A freewheel stop can be used with a stop command and by setting
the FFt parameter. When a stop command is given and the frequency
drops below the frequency set with the FFt parameter, the drive
controller will freewheel stop.
DC Injection Braking
DC injection braking can be activated at the end of each stop cycle
(Adc = Yes) or DC injection braking can be obtained by closing the
logic input assigned to the DC Injection Braking function (setting it to
state 1).
Figure 17: Reference Switching Wiring Diagram
COM
0–20 mA
4–20 mA
+10AI 1LI x + 24 AI 2
LIx contact open, reference = AI2
LIx contact closed, reference = AI1
- +