Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
84
PI Error
When configured for PI error, OPE, the analog output provides a
signal proportional to the PI regulator error as a percentage of the
sensor range being used for the PI feedback, (maximum feedback
minus minimum feedback). The minimum configured value, AOL,
corresponds to – 5%, while the maximum configured value, AOH,
corresponds to +5%. Zero corresponds to (minimum value +
maximum value) / 2, (AOL+AOH) / 2.
PI Integral Error
When configured for PI integral error, OPI, the analog output provides
a signal proportional to the PI integral error. The minimum configured
value, AOL, corresponds to the low speed setting, LSP, while the
maximum configured value, AOH, corresponds to the high-speed
setting, HSP.
Motor Power
When configured for motor power, OPR, the analog output provides a
signal proportional to power drawn by the motor. The minimum
configured value, AOL, corresponds to 0% of the nominal motor
power, while the maximum configured value, AOH, corresponds to
200% of the nominal motor power.
Motor Thermal State
When configured for motor thermal state, THR, the analog output
provides a signal proportional to the thermal state of the motor
calculated by the drive controller. The minimum configured value,
AOL, corresponds to 0% of the motor thermal state, while the
maximum configured value, AOH, corresponds to 200% of the motor
thermal state.
Drive Thermal State
When configured for drive thermal state, THD, the analog output
provides a signal proportional to the thermal state of the drive
controller. The minimum configured value, AOL, corresponds to 0%
of the drive controller thermal state, while the maximum configured
value, AOH, corresponds to 200% of the drive controller thermal
state.