Schneider Electric ALTIVAR 58 TRX Guia de Instalação Página 48

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 126
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 47
© 1998–2003 Schneider Electric All Rights Reserved
Chapter 2—Menus VVDED397047USR6/03
3—Drive Menu 06/2003
48
Ramp Type rPt
Defines the type of acceleration
and deceleration ramps.
LIN - S - U LIN
LIN: linear S: S ramp U: U ramp
NOTE: DecRamp
Coeff is only
available if fast
stop is enabled.
DecRamp Coeff dCF
Coefficient for reducing the
deceleration ramp time when a
logic input has been assigned to
the Fast Stop function.
1 to 10 4
For example:
If dec=20 s, setting dCF to 2 results in a 10 s dec ramp
setting.
Table 11: 3—Drive Menu Parameters (continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 14).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material
Handling, Yes for General Use and Variable torque.
[4]
This parameter is not available on 125–500 hp drive controllers.
[5]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle
ratings of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
50/60
Time
0
1/5
ACC/deC
ACC/deC
Motor
Frequency (Hz)
1/5
ACC/deC
S ramp
fn
f (Hz)
t
fn
f (Hz)
t
T1
T1
U Ramp
Acc
T1 = 1/Acc
Dec
T1 = 1/Dec
Vista de página 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 125 126

Comentários a estes Manuais

Sem comentários