Schneider Electric ALTIVAR 58 TRX Guia de Instalação Página 47

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 126
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 46
© 1998–2003 Schneider Electric All Rights Reserved
VVDED397047USR6/03 Chapter 2—Menus
06/2003 3—Drive Menu
47
Type of stop Stt
Type of stop:
STN–FST
NST–DCI
STN
When a stop is requested, the type of stop defined by this
parameter is activated until the FFt threshold (2—Adjust
menu) is reached. Below this threshold, freewheel stop is
activated.
Stn: On decel ramp
Fst: Fast stop
Nst: Freewheel stop
Dci: DC injection stop
NOTE: Switch Ramp 2 is not available if LI is assigned to
ramp switching.
NOTE: This parameter, Stt, cannot be accessed if the R2
relay or a logic output is assigned to the “BLC: Brake Logic”
function.
Table 11: 3—Drive Menu Parameters (continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 14).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material
Handling, Yes for General Use and Variable torque.
[4]
This parameter is not available on 125–500 hp drive controllers.
[5]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle
ratings of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
Vista de página 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 125 126

Comentários a estes Manuais

Sem comentários