Catch On Fly FLr Allows a smooth restart after:
• Brief loss of input power
Yes - No No
• Fault reset or automatic restart
• Freewheel stop or DC injection braking with a logic input
• Momentary interruption of the drive controller output
If relay R2 is assigned to the Brake Logic function, FLr will always be set to
No.
Cont. Stop StP Controlled stop upon loss of input phase. This
function is only operational if the IPL parameter
(Input Phase Loss) is set to No. If IPL is set to
No - NMS -
FRP
No
Yes, leave StP set to No. Possible choices:
• No: loss of input phase causes drive controller to trip
• NMS: Maintenance of DC bus: the DC bus is kept energized by
regenerating the kinetic energy from the machine inertia, until the USF
(Undervoltage) fault appears.
• FRP: Following a ramp: deceleration following the programmed ramp,
either dEC or dE2 until the motor stops or the USF (Undervoltage) fault
appears. This operation is not available on the ATV58•U09M2, U18M2,
U29M2 and U41M2.
RampNotFoll Sdd This function can be accessed if feedback via tachogenerator or
pulse generator is programmed. When enabled, it is used to lock
the speed controller if a speed error is detected (difference
between the stator frequency and the measured speed).
Yes / No options.
No
Table 21: 6—Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
Menu
6
AUTOMATIC RESTART
• Automatic catch on the fly must only be used on machines or
installations where automatic restarting will not endanger
personnel or equipment.
• Equipment operation must conform with national and local safety
regulations.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.
WARNING