6FAULT MENU
This menu is only accessible when the access locking switch is in the
position. Modifications can only be made when the motor is stopped.
Table 21: 6Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
Auto Restart
Atr
This function allows an automatic restart of the
drive controller if the cause of the fault has
disappeared and a run command is maintained.
Yes - No No
An automatic restart is possible after the following faults:
Input overvoltage
DC bus overvoltage
External fault
Serial link fault
Loss of 420 mA follower
Motor phase loss
Motor overload (after the thermal state has decreased below 100%)
Drive controller overheating (when the thermal state has decreased
below 70%)
Motor overheating (when the thermal sensor resistance is less than 1500
ohms)
Communication fault.
When the Auto restart is active, the fault relay remains energized. If the fault
has disappeared, the drive controller will attempt to restart the motor after a
delay of 30 s. If the drive controller remains faulted after 6 attempts, the fault
relay de-energizes and the drive controller must be reset by cycling power.
Menu
6
AUTOMATIC RESTART
Automatic restart can only be used for machines or installations
that present no danger in the event of automatic restarting, either
for personnel or equipment.
Equipment operation must conform with national and local safety
regulations.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.
WARNING