VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
61
Reference Switching (Auto/Manual)
Switching between two references (at AI1 and AI2) by a logic input
command. When the logic input is closed (set to state 1), AI1 is enabled.
This function automatically assigns AI2 to Speed Reference 2.
Figure 17: Reference Switching Wiring Diagram
Freewheel Stop (Coast to Stop) / Run Permissive
A logic input can be assigned to the Freewheel Stop / Run Permissive
(NST) function. The drive controller will not run until the logic input is
closed. Opening the logic input assigned to the function (setting it to state
0) causes the drive controller to stop applying power to the motor and the
motor to coast to a stop. When the logic input is open, NST is displayed
in the Drive state screen on the keypad display to indicate that a
freewheel stop has been requested. The drive controller will not run until
the logic input is closed. This can be used with the Forced Local function
for drive controllers on communication networks.
A freewheel stop can be used with a stop command and by setting the
FFt parameter. When a stop command is given and the frequency drops
below the frequency set with the FFt parameter, the drive controller will
freewheel stop.
DC Injection Braking
DC injection braking can be activated at the end of each stop cycle
(Adc = Yes) or DC injection braking can be obtained by closing the logic
input assigned to the DC Injection Braking function (setting it to state 1).
COM
020 mA
420 mA
+10AI 1LI x + 24 AI 2
LIx contact open, reference = AI2
LIx contact closed, reference = AI1
- +