Mounting
975-0239-01-01 4–7
This manual for use by qualified personnel only
Mounting the Controller
The Xantrex XW SCC can be mounted to either the side or the top of the power
distribution panel. The power distribution panel has keyhole slots and screw
holes for side mounting, and two pairs of conduit holes for top mounting the
Xantrex XW SCC.
To mount the Xantrex XW SCC to the side of the power distribution panel:
1. Back out the top side screw on the Xantrex XW SCC by ¼-inch.
2. Remove the lower side screw on the Xantrex XW SCC.
3. Holding the unit against the side of the power distribution panel, insert the
top side screw into one of the two keyhole slots on the side of the power
distribution panel and pull the unit down into the slot.
4. Insert the lower side screw through the hole on the inside of the power
distribution panel and into the side of the Xantrex XW SCC.
5. Tighten the lower side screw to secure the Xantrex XW SCC.
To mount the Xantrex XW SCC to the top of the power distribution panel:
1. Remove a pair of knockouts from the top of the power distribution panel.
2. Remove the bottom knockouts from the Xantrex XW SCC.
3. Align the knockouts on the power distribution panel and Xantrex XW SCC,
and secure the unit with two locking strain reliefs or threaded connectors.
In a stand-alone installation, the Xantrex XW SCC is mounted using three
#10 × ½-inch or #12 × ½-inch (12.5 mm) pan-head screws.
Figure 4-4 Knockout Dimensions
34.52 (1 3/16) & 27.78 (1 1/16)
DUAL KNOCKOUT
26.47
(1)
31.50 (1 ¼)
20.20
(¾)
50.00 (2) 50.80 (2)
25.9 (1)
27.78 (1 1/16)
KNOCKOUT
25.0 (1)
50.80 (2)
26.47 (1)
50.00 (2)
KNOCKOUT
27.78 (1 1/16
34.52 (1 3/16) & 27.78 (1 1/16)
2 PL
DUAL KNOCKOUT
34.52 (1 3/16) & 27.78 (1 1/16)
2 PL
DUAL KNOCKOUT
Single knockouts intended
for BTS and network cables