Alternate System Configurations
C–6 975-0239-01-01
This manual for use by qualified personnel only
Generator Wiring to the Inverter
WARNING: Shock Hazard
Before making any electrical connections, ensure both the AC and DC
disconnect devices are in the OPEN (disconnect) position.
Important: If the load is too big for the inverter to operate from battery power,
do not install the load in the inverter powered electrical panel.
Figure C-5 Generator Wiring directly to the Inverter
Torque all inverter terminal block connections to
25 inch-pounds.
This illustrates an example only.
Actual wiring requirements may vary.