Step 5: Installing Additional Inverters
975-0239-01-01 2–43
This manual for use by qualified personnel only
Parts List for a Triple-Inverter Configuration
1 x Xantrex XW Power Distribution Panel (Xantrex XW PDP) and Accessory kit
(mounts to first unit).
1 x 865-1020 Xantrex XW PDP Connection Kit for INV2.
The following items are required for the third inverter (furthest from Xantrex XW
PDP) and should be sourced and prepared prior to the installation. (Note that all
wiring will have to be custom cut to fit the third unit. Wiring supplied with the
extension kit is intended for a second inverter in a two inverter system.)
For a Single AC Source Installations:
1 x 865-1024 Xantrex XW Conduit Box for inverter
1x 250 A DC breaker (Master packs available from manufacturer part
number: 865-1065)
1.0 m (39") x CAT5 network cable for inverter AC Sync
1.0 m (39") x CAT5 network cable for Xantrex Xanbus communication
0.5m (20") x #4 AWG, 600 V, 105°C stranded green wire for ground
connection
Or for a Dual AC Source Installations:
1 x 865-1020 Connection Kit for INV2 (contains AC and DC breakers
required for third inverter).
2.3m (91") x #6 AWG, 600 V, 105°C Black stranded wire for L1 Gen (AC2).
2.3 m (91") x #6 AWG, 600 V, 105°C Red stranded wire for L2 Gen (AC2).
The following are required for both Single and Dual AC source Installations:
2.2 m (87") x #6 AWG, 600 V, 105°C stranded white wire for neutral
2.2 m (87") x #6 AWG, 600 V, 105°C Black stranded wire for L1 Grid (AC1).
2.2 m (87") x #6 AWG, 600 V, 105°C Red stranded wire for L2 Grid (AC1).
2.3m (91") x #6 AWG, 600 V, 105°C Black stranded wire for L1 (AC2 Load).
2.3 m (91") x #6 AWG, 600 V, 105°C Red stranded wire for L2 (AC2 Load).
2.4 m (95") x #6 AWG, 600 V, 105°C Red stranded wire for AC Load.
1.6m (62") #4/0 AGW, 105°C, Red stranded with #4/0 x 3/8 lugs crimped at
each end for the positive battery cable.
1.6m (62") #4/0 AGW, 105°C, Black stranded with #4/0 x 3/8 lugs crimped at
each end for the negative battery cable.
External Bypass Switch - The Xantrex XW Power Distribution Panel does not
have enough breaker locations to accommodate bypass breakers in a
triple-inverter system. Therefore, an external Bypass Switch may be needed.
See Figure 2-34 on page 2–48 for an illustration of how to wire an External
Bypass Switch.