Step 4: Wiring the Inverter
975-0239-01-01 2–25
This manual for use by qualified personnel only
AC Wiring to the Xantrex XW Power Distribution Panel
To connect the Xantrex XW Power Distribution Panel to the inverter:
1. Connect the neutral wire first to the N-LOAD terminal. Connect the wires
labelled “INV1 N-LOAD (SPLIT PHASE)”, “INV1 L1-LOAD, and “INV1
L2-LOAD” (from the L1 and L2 terminals on the input (top) side of the output
breaker and the neutral bus) to the AC Load (L1-LOAD, N-LOAD, L2-LOAD)
terminals on the inverter.
2. Connect the wires labelled “INV1 L1-GRID” and “INV1 L2-GRID” to the
inverter. If the AC source will be the utility grid, connect to the GRID (AC1)
terminals (L1-GRID, L2-GRID). If the system will be off-grid and the only AC
source will be a generator, these wires can be connected to the GEN (AC2)
terminals (L1-GEN, L2-GEN). No additional neutral connection is needed
when using the Xantrex XW Power Distribution Panel. (Additional neutral
terminals (N-GRID, N-GEN) are provided on the inverter for installations that
do not use the Xantrex XW Power Distribution Panel.)
3. Connect L1 (from the L1 output Power Distribution Bar) and L2 (from the L2
output Power Distribution Bar), Neutral, and Ground to the sub-panel that
supplies power to inverter loads.
4. Connect the ground wire between the Xantrex XW Power Distribution Panel
and the utility grid AC panel. Connect Neutral from the Xantrex XW Power
Distribution Panel to the utility grid AC panel. Connect L1 and L2 from the
input side of the AC1 Breaker (L1 and L2 Power Distribution bars) to the utility
grid AC Panel.
Important: The Xantrex XW Inverter/Charger is provided with fixed disconnect
limits for voltage and frequency. These limits are fixed when the unit is exporting
power to the grid. The unit shall not be aggregated such that it can export more
than 30 kW on a single point of common connection.
Important: Both lines of input power must be connected in order for the Xantrex
XW Inverter/Charger to operate. For example, L1 and L2 of Grid Input and/or L1
and L2 of Gen Input need to be connected.