Installation Instruction 66571764GB3 Fire Detection 50
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
20.6 FXS panel external connections, ALC
Serial (RS485) communication with other FX panels (2 pcs)
Clean contact signal inputs (4 pcs), function configurable
INFO communication
REPX-OB
or
MCOX-OB
or
ZLPX-IC
Master
controller
FX-MC2
Loop controller
FX-ALCA, FX-ALCB
0…1 pcs
Loop controller
FX-CLC
0…1 pcs
Output controller
FX-OCA
0…1 pcs
Input/output
controller
FX-IOC
0…1 pcs
Serial (RS232) communication with printer or maintenance tool (PC)
External communication (not in ZLPX-IC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel,
separately monitored for low voltage
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
FX-ALCA: One addressable detection circuits, with 126 addresses
FX-ALCB: Two addressable detection circuits, each 126 addresses
FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA
FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each
Monitored output (Bells, sounders, beacon), 500 mA
Power supply output 24 VDC, short circuit protected, 500 mA
USB connection, maintenance tool (PC)
For each FX-CLC: 16 Conventional detection circuits, function configurable
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Ethernet connection, INFO communication: Future option
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
INFO communication
Note!
The max. current consumption of the FX - control
panel (with PSB- power supply board), all loops and
addresses and all control panel outputs is 1 A in
standby condition and 4.0 A in alarm condition. The
standby time required for the system may limit the
max. load of the outputs.
Note!
The max. current consumption of the FXM - control panel
(with PSA- power supply board), all loops and addresses
and all control panel outputs is 0.5 A in standby condition
and 2.2 A in alarm condition. The standby time required
for the system may limit the max. load of the outputs.