
Installation Instruction 66571764GB3 Fire Detection 31
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
12.5 Compatible detectors and manual call points
Compatibility of detectors with the CLC conventional line is determined by the following factors:
- Supply voltage range
- Current consumption in standby condition
- Voltage across the detector in alarm condition
- Series resistance (either in the detector or in the base)
- End-Of-Line resistor
The voltage supplied by the CLC to the conventional line is 21 Vdc to 24 Vdc. The maximum allowable voltage
drop in the cable is 21 V minus the lowest operating voltage of the connected devices.
If the line goes through an Exi barrier, the maximum allowed cable resistance and current consumption is less than
for a normal line.
The following table shows the required series resistor for a number of detector voltages (in alarm condition), the
two allowed EOL types and whether or not a Exi barrier is connected to the loop.
Conventional Line
Threshold voltage over
detector / allowed serial
resistance in alarm
condition
Input Line
When CLC input is configured as input line, only EOL 4k7 can be used. If it is configured as Exi-area input, line
alarm resistance values are different. See table below and chapter 12.2.2.
(e.g. 4k87 and 2k94 in parallel =
(e.g. 4k87 and 2k94 in parallel =
Comentários a estes Manuais