Installation Instruction 66571764GB3 Fire Detection 15
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
8. Preliminary checks
8.1 General
The aim of the preliminary checks is to assure that the settings are correct and that the control panel has not
suffered any defects during transportation or installation. This is obviously most easy to do when no external cables
are connected, except for the necessary power supply connection.
8.2 Preliminary checks
1. Check that all power is disconnected from the control panel.
The cable from the transformer to the power supply component
board is disconnected from the terminal 30VAC on the component
board.
The battery cable is disconnected from the battery terminal BATT
on the component board.
FXS: PI1 and PI2 are disconnected.
2. Check that the mains cable is connected to the mains terminal.
3. Check that the separate fuse reserved for the control panel is in its
place.
P
O
2
+
2
4
V
-
P
O
1
+
2
4
V
-
B
A
T
T
+
-
MC2 jumper settings
Side CPU not in use’ jumper should not be in place in FX
NET systems in seeing panels provided with a fire routing
equipment. In case of a system fault the assistant processor
takes care of the system communication. If there is a fire
alarm in one of the system panels the assistant processor
controls:
o the fire routing output CO1 of the MC2 unit
(independent of the configuration of the CO1)
o the fire alarm device output of the MC2 unit
(independent of the configuration of the output)
o the general fire alarm LED
o the panel specific fire alarm LED (LB2-32)
o the buzzer of the panel
1. Check the following settings:
The “CONF” jumper is not in place.
The “PULSED” jumper is not in place (for continuous
alarm device signal) or in place (for pulsing alarm device
signal).
The “PROG” jumper is not in place.
The “PI IN USE” jumper is not in place.
FXS: PI IN USE in place!
The “IOC’S” jumper is correctly set for the number of
IOC’s and OCA’s in the panel.
The “LC’S” jumper is correctly set for the number of
SLC’s, ALC’s and CLC’s in the panel.
2. Check also that there is a 4.7 k end-of-line resistor in
the terminals for the monitored output line.
3. Check also that there is a 4.7 k end-of-line resistor in
the terminals for the monitored input lines.
RS485
Gnd - +
RS232
Tx Rx Gnd
SYS 1
Gnd - +
SYS 2
Gnd - +
SIDE CPU NOT IN USE
IOC’S LC’S
CONFIG
PULSED
PR OG U PD
PI IN U SE