Installation Instruction 66571764GB3 Fire Detection 19
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
10. Cable handling and preliminary measurements
WARNING!
Check by measuring that there is no power in the cables.
10.1 Cable handling and measurements
At every stage of commissioning, power must be
disconnected from the control panel before the cables are
installed.
First disconnect the battery then the
mains.
1. Peel off the cable plastic and protective shields. Be careful
not to let peeling remains drop onto the component board
or between the back wall of the cabinet and the
component board.
Loop 2
A+ A-
Loop 2
B+ B-
Loop 1
A+ A-
Loop 1
B+ B-
PO 2
+24V-
PO 1
+24V-
>1MΩ
Loop 2
A+ A-
Loop 2
B+ B-
Loop 1
A+ A-
Loop 1
B+ B-
PO 2
+24V-
PO 1
+24V-
>1MΩ
>1MΩ
2. Make sure that the cables have been marked and that the
markings can be seen after the peeling.
3. If the cables used are shielded, measure, before
connecting the shield that the resistance between the
shield and the cabinet ground exceeds 1 M. If the
resistance is smaller, the cable shield is in contact with the
construction of the building:
- The outer sleeve of the cable has been damaged.
- The protective shield is in connection to the
construction of the building in a detector socket.
Repair the fault. Then connect the cable shield to the
cabinet ground.
4. Measure for each cable: the resistance between the cable
shield and the wires. The resistance must exceed 1 M. If
the value is smaller, the earth leak must be located and
repaired.
5. If the cables used are not shielded, measure the
resistance between the wires and cabinet ground. It must
also exceed 1 M.