Installation Instruction 66571764GB3 Fire Detection 13
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
6. Connecting main power supply
Connect the mains supply (230 VAC)
There must be a separate fuse (10 A) for the control panel power
supply.
Cable 3 x 1.5 mm².
Note!
FXS has not any built-in power supply. The power is fed to the FXS
panel from FX or FXM power supply unit using 2 power lines. The
power supply PI1 and PI2 inputs in FXS are on the MC2 board. Both
must be connected and the “PI in use”- jumper on MC2 must be set.
+ - ADL + - PO
- +IN1 + -PI2 + -PI1
FXS panel: MC2 board
PO 2
+24V-
PO 1
+24V-
FX or FXM panel:
PSA or PSB board