Chapter 3 Connecting to a Controller
Modbus communications by modem l 41
3. Set Modbus communication parameters for your network.
Ÿ The Modbus Port setting must show the computer port connected
to the modem; otherwise, NxT wont be able to locate it.
v For more information, see the Modbus table on page38.
Ÿ The Modbus configuration must send exactly 10 bits per data
package to your modem.
Modems generally expect 10 bits in a data package; however, the
Modbus defaults (Even parity, RTU mode, and one stop bit) send
11 bits per package.
Change the Modbus settings to provide 10 bits per data package or
NxT will not be able to communicate with the modem.
Alternatively, if your modem supports large data packages, you
can set its DIP switches to allow 11 bits per data package (see your
modems manual).
These Modbus configurations provide 10 bits per data package:
4. Choose settings for your modem.
The controller must have the same Modbus settings as the computer. Set
Modbus parameters for your PLC with the Ports tab of the Controller
Configuration window.
v For more information, see Controller configuration - Ports tabon page62.
Parameters ASCII Mode ASCII Mode RTU Mode
Start Bit 1 bit 1 bit 1 bit
Data 7 bits 7 bits 8 bits
Stop Bits: 1 1 bit 1 bit
2 2 bits
Parity: None 0 bits 0 bits
Odd or Even 1 bit
Total 10 bits 10 bits 10 bits