ProWORX NxT Users Guide
38 l Configuring Modbus communications
Ø To select and configure Modbus communications:
1. From the ProWORXNxT Title Screen or the Offline Network Editor,
on the Controller menu, click Communication Setup. The
Communications Setup dialog box appears.
2. From the Interface list on the left, select Modbus.
3. Set the parameters for your Modbus communication system:
Ÿ Port: Identifies which serial port on your PC is connected to the
controller or modem (if you are connecting to the controller
through one). Default is COM1.
Ÿ Baud: Sets the data transfer speed of your PCs serial port in bits
per second. The PC and controller must be set to the same baud.
Default is 9600.
Ÿ Parity: Adds a check bit to a packet to make the number of binary
ones always either odd (Odd parity) or even (Even parity). If parity
is set to None, the check bit is not added. The PC and controller
must use the same parity. Default is Even.
Ÿ Stop Bit: Sets the number of bits at the end of a packet prepares the
receiving device for the next packet. The PC and controller must
use the same number of stop bits. Default is 1.
Ÿ Timeout: Specifies the length of time the PC will wait for successful
communication with a controller before displaying an error
message. Default is 2 seconds.
These parameters affect
the PC only. They must
match the parameters
set for the controller.
After you choose a com-
munication system from
the list on the left, its op-
tions appear on the right.
To select Modbus com-
munications, the Modem
Type must be set to None.