Schneider Electric FX 3NET Guia do Utilizador Página 35

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 64
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 34
Planning Instruction 66571758GB0 Fire Detection 35
Schneider Electric Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011
© 2009 Schneider Electric. All rights reserved.
9. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET Technical data
9.1 Technical data, standard panels
FX 3NET FXL 3NET FXM 3NET FXS 3NET
Dimensions (h*w*d) [mm] 578 x 425 x 130 328 x 425 x 130 328 x 417x79
Weight (fully equipped, excl. batteries) 11 kg 12 kg 6 kg 4.4 kg
IP Rating IP30
Operating ambient temperature +5…+40°C
Storage ambient temperature 0…+50°C
Maximum ambient humidity 95% RH
Backframe material sheet steel
Cover material plastic
Cover colour bluish grey
Number of SLC, CLC, IOC and OCA boards
- FX-SLC and/or FX-CLC together 4 4 2 1
- FX-IOC 4 4 2 1
- FX-OCA 4 4 2 1
- REPX-OB 1 1 1 1
- MCOX-OB 1 1 1 1
- ZLPX-IC 1 1 1 1
- FX-SLC, FX-CLC, FX-IOC, REPX-OB,
MCOX-OB, ZLPX-IC together
5 9 2 1
Number of addresses per detection circuit
Detector addresses
IO-module addresses
159
159
Total number of detectors and manual call
points connected to the panel
512 512 396
Mains supply voltage 230 VAC ±10% / 50 ... 60Hz
Mains supply power 160 VA 80 VA
NA
Operating voltage range 21 ... 30 Vdc
Maximum current consumption in standby
condition
1.0 A @ 24 Vdc 0.5 A @ 24 Vdc 0.5 A @ 24 Vdc
Maximum current consumption in alarm
condition
4.0 A @ 24 Vdc 2.2 A @ 24 Vdc 1 A @ 24 Vdc
Applied standard
EN54-2
EN54-4
EN54-2
Note!
FXS 3NET requires a power feed from an FX 3NET, FXL 3NET or FXM 3NET panel. Available
power from that panel may restrict the current consumption of the FXS panel.