Tech Data Sheet D01687GB3 Fire Detection 3
Schneider Electric Pelco Finland Oy Sokerilinnantie 11C, 02600 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103
www.pelco.com/nordic
Document Number D01687GB3 50 2012
© 2009 Schneider Electric. All rights reserved.
Construction of the FX 3NET panels
Control panels
Note
FX 3NET
FXL 3NET
FXM 3NET
FXS 3NET
Base
units
FX-UI2 user interface
1
1
1
1
FX-MC2 master controller
1
1
1
1
FX-PSA power supply
-
-
1
-
Note 1
FX-PSB power supply
1
1
-
-
Note 1
Card slots
5
9
2
1
Note 2
Card
slot
options
Loop controllers 1…4 pcs together
- FX-SLC, 2 AP200 series loops
- FX-CLC, 16 conventional loops
0…4
0…4
0…4
0…4
0…2
0…2
0…1
0…1
Note 3
Note 6
Control units 1…4 pcs together
- FX-IOC
- FX-OCA
0…4
0…4
0…4
0…4
0…2
0…2
0…1
0…1
REPX-OB protocol repeater
0…1
0…1
0…1
0…1
MCOX-OB logic control unit
0…1
0…1
0…1
0…1
ZLPX-IC
0…1
0…1
0…1
0…1
UI2 place
options
Display units
- FX2-LB32 panel display units
- FX-LB80 zone display units
0…1
0…1
0…1
0…1
0…1
0…1
0…1
0…1
Note 4
Battery
space
Batteries 2 pcs
12 V/17 Ah
- 2 pcs
12 V/12 Ah
- Note 5
Note 1
Note 1
FXS requires a power feed from an FXM, FX or FXL panel. Available power from that panel may restrict the
current consumption of the FXS panel.
Note 2
Card slots are for SLC, LC, CLC, IOC, OCA, REPX-OB, MCOX-OB and ZLPX-IC option boards.
Note 3
Loop controllers are optional. The maximum number of loop controllers is 1 in FXS, 2 in FXM and 4 in FX and
FXL.
Note 4
Only 1 display unit per panel.
The FX-LB80 is used in the UK.
Note 5
Batteries of the FXL 3NET panel are installed in a separate FX BAT cabinet.
Note 6
SLC Loop controller can be configured to work as LC Loop controller in order to be able to use series 200
devices in the loop. When configured as LC, loop capacity (number of addresses and loop resistance value) is
as specified for LC.
Series 200 loop devices can be used in SLC loop with AP200 devices.
In this case the following rules apply:
- There can be maximum 20 pcs of series 200 devices in the loop (among AP200 devices)
- The maximum loop resistance is 40 Ohm.