Tech Data Sheet D01688GB1 Fire Detection 3
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number D01688GB1 10 2012
© 2009 Schneider Electric. All rights reserved.
Construction of the FX 3NET panels
Control panels
Note
FX 3NET
FXL 3NET
FXM 3NET
FXS 3NET
Base
units
FX-UI2 user interface
1
1
1
1
FX-MC2 master controller
1
1
1
1
FX-PSA power supply
-
-
1
-
Note 1
FX-PSB power supply
1
1
-
-
Note 1
Card slots
5
9
2
1
Note 2
Card
slot
options
Loop controllers 1…4 pcs together
- FX-ALCA, 1 Intellia loop
- FX-ALCB, 2 Intellia loops
- FX-CLC, 16 conventional loops
0…4
0…4
0…4
0…4
0…4
0…4
0…2
0…2
0…2
0…1
0…1
0…1
Note 3
Control units 1…4 pcs together
- FX-IOC
- FX-OCA
0…4
0…4
0…4
0…4
0…2
0…2
0…1
0…1
REPX-OB protocol repeater
0…1
0…1
0…1
0…1
MCOX-OB logic control unit
0…1
0…1
0…1
0…1
ZLPX-IC
0…1
0…1
0…1
0…1
UI2 place
options
Display units
- FX2-LB32 panel display units
- FX-LB80 zone display units
0…1
0…1
0…1
0…1
0…1
0…1
0…1
0…1
Note 4
Battery
space
Batteries 2 pcs
12 V/17 Ah
- 2 pcs
12 V/12 Ah
- Note 5
Note 1
Note 1
FXS requires a power feed from an FXM, FX or FXL panel. Available power from that panel may restrict the
current consumption of the FXS panel.
Note 2
Card slots are for ALCA, ALCB, CLC, IOC, OCA, REPX-OB, MCOX-OB and ZLPX-IC option boards.
Note 3
Loop controllers are optional. The maximum number of loop controllers is 1 in FXS, 2 in FXM and 4 in FX and
FXL.
Note 4
Only 1 display unit per panel.
The FX-LB80 is used in the UK.
Note 5
Batteries of the FXL 3NET panel are installed in a separate FX BAT cabinet.