
Communications Adapter Register Mapping
20
14
2.1 I/O words and ID–code
After the I/O module is powered–up, the identification code (ID code) of the
module base is automatically read by the communication adapter. The ID–code
provides the Interbus master with the type of data (input or output) and the number
of words in the message for each module. After the I/O modules identification
codes are received, the Interbus master will automatically begin the execution of
I/O data communication in real time.
The length is in each case expressed in I– or O–words, with the higher number
being the decisive factor. The number of words it can contain is: 1 to 10, 12, 14,
16, 24 or 32 words.
The ID–code for the 170 ADM 350 10 is 0103 hex.
H 01 = Length statement, indicating that the module needs one word (I–
or O–word) for data transfer
H 03 = Module Type, indicates that this module has inputs and outputs
Table 2 I/O Base Word Number and ID Code (analog I/O bases)
Description
Function I–Words O–Words ID Code
170 AAI 140 00 16 input channels 16 4 1033 hex
1651 dec
170 AAI 520 40 4 input channels, RTD, Therm. 4 4 0433 hex
0451 dec
170 AAO 120 00 4 output channels, 0 ... 20 mA 5 0531 hex
0549 dec
170 AAO 921 00 4 output channels, 4 ... 20 mA 5 0531 hex
0549 dec
170 AMM 090 00 4 inputs, 2 outputs (discrete)
4 input & 2 output channels (ana-
log)
1
4
1
4
0533 hex
0551 dec
Example
Comentários a estes Manuais