Interbus with TSX Momentum Overview
20
12
1.4 Configuration Limits
Table 1 Interbus Configuration Limits for Standard PLC (e.g. TSX Quantum)
Parameters
Limitations
max. number of nodes (slaves) 256
max. distance between 2 nodes Twisted pair, shielded = 400 m (1 200 ft)
max. distance between 2 nodes Fiber optic (HCS) = 300 m (900 ft)
max. distance between 2 nodes fiber optic cable, polymer fiber = 50 m (150 ft)
max. length of network 13 km (8 mi)
max. number of I/O points 4096
Transfer Rate 500 kBits/s
Data throughput for 1 000 I/O points ~ 4 ms